6 Set up with the display and adjustment module PLICSCOM

VEGACAL 64 • Profibus PA

30031-EN-130917

In the main menu item "Basic adjustment", the individual submenu

items should be selected one after the other and provided with the

correct parameter values.

Tip:

If the display and adjustment module remains on the probe as a

display, we recommend saving the sensor data in the display and

adjustment module.
Use the function "Copy sensor data".
Start your parameter adjustment with the following menu items of the

basic adjustment:

To be on the safe side, note the adjustment values for full and empty.

If an adjustment procedure fails, it is not necessary to again carry out

a level change.
These values can be helpful if the electronics has to be exchanged.

%

Value

Empty adjustment
Full adjustment

Tab. 1: Adjustment protocol

Tip:

For min. adjustment the vessel should be as empty as possible, and

for max. adjustment, as full as possible. If the vessel is already full,

start with max. adjustment.
Note:

If possible, the vessel should be as empty as possible for min. adjust-

ment.
Proceed as follows:
1. Move from the measured value display to the main menu by

pushing [OK].

Basic adjustment
Display
Diagnostics
Service
Info

2. Select the menu item "Basic adjustment" with [->] and confirm

with [OK]. Now the menu item "Min. adjustment" is displayed.

Min. adjustment
0.00 %
=
0.0 pF

54.5 pF

3. Prepare the adjustment value for editing with [OK]. Move to the

selection window with [OK].

Carry out min. adjustment