VEGA VEGASON 62 4 … 20 mA_HART - four-wire User Manual

Page 16

Advertising
background image

16

4 Mounting

VEGASON 62 • 4 … 20 mA/HART - four-wire

28779-EN-130417

By using a standpipe (surge or bypass tube), the influence of vessel

installations, foam generation and turbulence is excluded.
Standpipes must extend all the way down to the requested min. level,

as measurement is only possible within the tube.

max.

min.

1

Fig. 14: Standpipe in the tank
1 Vent hole: ø 5 … 10 mm (0.197 … 0.394 in)

VEGASON 62 can be used from tube diameters of 50 mm (1.969 in).
Avoid large gaps and thick welding joints when connecting the tubes.

Generally carry out a false echo storage.
Measurement in a standpipe is not recommended for extremely

adhesive products.

Standpipe measurement

Advertising