A special version of VEGAPULS 66 is available for each area of
application. The version with flange and standpipe is particularly
suitable for the measurement of solvents and liquid gases.

The standpipe antenna is also suitable for vessels with foam
generation or for measurement of products with low dielectric figures
(DK > 1.6).

Measurement in a standpipe is not recommended for very adhesive
products.

For pressures up to 160 bar (2320 psi) and temperatures up to 400 °C
(752 °F) there are graphite seals and ceramic antenna cones
available.

The antenna of the radar sensor emits short radar pulses with a
duration of approx. 1 ns. These pulses are reflected by the product
and received by the antenna as echoes. The running time of the radar
pulses from emission to reception is proportional to the distance and
hence to the level. The determined level is converted into an
appropriate output signal and outputted as measured value.

Power is supplied via the H1 Fieldbus. A two-wire cable according to
Fieldbus specification serves as carrier of both power and digital data
for multiple sensors. This cable can be operated in two versions:

l

via an H1 interface card in the control system and additional power
supply

l

via a Linking device with HSE (High speed Ethernet) and
additional power supply according to IEC 61158-2

The DD (Device Descriptions) and CFF (capability files) necessary for
planning and configuration of your FF (Foundation Fieldbus) commu-
nication network are available in the download area of the VEGA
homepage www.vega.com under "Services - Downloads - Software -
Foundation Fieldbus
". The appropriate certificates are also available
there. A CD with the appropriate files and certificates can be ordered
via e-mail under [email protected] or by phone from one of the VEGA
agencies under the order number "DRIVER.S".

The backlight of the indicating and adjustment module is powered by
the sensor. Prerequisite is a certain level of operating voltage.

The data for power supply are specified in chapter "Technical data".

The optional heating requires its own operating voltage. You can find
detailed information in the supplementary instructions manual "Heating
for indicating and adjustment module
". This function is generally not
available for approved instruments.

3.3 Operation

VEGAPULS

66 can be adjusted with different adjustment media:

Functional principle

Power supply and bus
communication

DD/CFF

10

VEGAPULS

66 standpipe version • Foundation Fieldbus

3 Product description

28744

-EN