2 Connecting to power supply

2.1 Plug assignments

Each respective wiring plan shows the assignment of the

individual pins of the plug connector depending on the signal

output. The chart shows the assignment of the individual

contact pins to the terminals of the sensor electronics.

3

1

2

4

Fig. 1: View to the pins of the plug insert with Foundation Fieldbus

1

- (Pin 1)

2

+ (Pin 2)

3

free (Pin 3)

4

Screen (Pin 4)

Contact pin

Colour connection

cable

Terminal, electro-

nics

1

Blue

2

2

Brown

1

3

free

free

4

Green/yellow

4