4 mounting, 1 general instructions – VEGA VEGACAP 64 - Relay (DPDT) User Manual

Page 11

Advertising
background image

11

4 Mounting

VEGACAP 64 • - Relay (DPDT)

30012-EN-130916

4 Mounting

4.1 General instructions

Make sure that all parts of the instrument coming in direct contact

with the process, especially the sensor element, process seal and

process fitting, are suitable for the existing process conditions, such

as process pressure, process temperature as well as the chemical

properties of the medium.
You can find the specifications in chapter "Technical data" and on the

nameplate.

In general the level switch can be mounted in any position. The instru-

ment must be mounted in such a way that the probe is at the height of

the requested switching point.

Before beginning the welding work, remove the electronics module

from the sensor. By doing this, you avoid damage to the electronics

through inductive coupling.

With threaded versions, the housing must not be used to screw in the

instrument. Applying tightening forces on the housing can damage its

internal parts.
Use the hexagon for screwing in.

Use the recommended cables (see chapter "Connecting to power

supply") and tighten the cable gland.
You can give your instrument additional protection against moisture

penetration by leading the connection cable downward in front of the

cable entry. Rain and condensation water can thus drain off. This ap-

plies mainly to outdoor mounting as well as installation in areas where

high humidity is expected (e.g. through cleaning processes) or on

cooled or heated vessels.

Fig. 4: Measures against moisture penetration

Do not hold VEGACAP 64 on the probe. Especially with heavy flange

versions or long rod versions, the sensor can be damaged simply by

the weight of the instrument.

Suitability for the process

conditions

Switching point

Welding work

Handling

Moisture

Transport

Advertising