6 Setup

VEGASWING 63 • - two-wire

29232-EN-130409

6 Setup

6.1 General information

The figures in brackets refer to the following illustrations.

With plastic housings, the switching condition of the electronics can

be checked when the housing cover is closed (control lamp). With the

basic setting, products with a density > 0.7 g/cm³ (0.025 lbs/in³) can

be detected. For products with lower density, the switch must be set

to > 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following indicating and

adjustment elements:

Signal lamp (1)

DIL switch for sensitivity adjustment (2)

Mode adjustment (A/B)

On the VEGATOR 536Ex, 537Ex, 636Ex signal conditioning instru-

ment, via the signal conditioning instrument (when used according to

WHG only mode A permitted).
The switching condition can be changed with the A/B switch. You can

set the required mode according to the "Function chart" (A - max. de-

tection or overfill protection, B - min. detection or dry run protection).

The switching delay can also be modified on the signal conditioning

instrument (VEGATOR 536Ex, 537Ex and 636Ex signal conditioning

instruments).
Note:

For test purposes, immerse the tuning fork of VEGASWING 63 always

in liquids. Do not test the function of VEGASWING 63 with your hand.

This can damage the sensor.

6.2 Adjustment elements

1

2

1
2

Fig. 14: Oscillator SWE60Z - two-wire output
1 Signal lamp (LED)

2 DIL switch for sensitivity adjustment

Function/Configuration