0 s

E

nter the requested parameter via the appropriate keys, save

your settings and jump to the next menu item with the [->] key.

A

linearization is necessary for all vessels in which the vessel

volume does not increase linearly with the level - e. g. with a
cylindrical or spherical tank - and the indication or output of the
volume is required. Corresponding linearization curves are
preprogrammed for these vessels. They represent the
correlation between the level percentage and vessel volume.
B

y activating the appropriate curve, the volume percentage of

the vessel is displayed correctly. If the volume should not be
displayed in percent but e.g. in l or kg, a scaling can be also
set in the menu item "Display".

L

inearisation curve

linear

E

nter the requested parameter via the appropriate keys, save

your settings and jump to the next menu item with the [->] key.

I

n this menu item you can enter an unambiguous designation

for the sensor, e.g. the measurement loop name or the tank or
product designation. In digital systems and in the documen-
tation of larger plants, a singular designation should be entered
for exact identification of individual measuring sites.

S

ensor-TAG

Sensor

W

ith this menu item, the Basic adjustment is finished and you

can now jump to the main menu with the [ESC] key.

H

igh sockets or vessel installations, such as e. g. struts or

agitators as well as buildup and weld joints on the vessel walls
cause interfering reflections which can impair the measure-
ment. A false echo storage detects and marks these false
echoes, so that they are no longer taken into account for the

Linearisation curve

Sensor-TAG

Gating out of false sig-
nals

VEGAFLEX

66 • 4 … 20

mA/HART - four-wire

29