Take note of the corresponding installation regulations for Ex

applications.

If screened cable is necessary, connect the cable screen on

both ends to ground potential. In the VEGABOX 01 or

VEGADIS 12, the screen must be connected directly to the

internal ground terminal. The ground terminal on the outside of

the housing must be connected to the potential equalisation

(low impedance).
If potential equalisation currents are expected, the connection

on the processing side must be made via a ceramic capacitor

(e.g. 1 nF, 1500 V). The low frequency potential equalisation

currents are thus suppressed, but the protective effect against

high frequency interference signals remains.

In Ex applications, grounding on one sensor side is recom-

mended, see EN 60079-14.

5.2 Connection procedure

Proceed as follows:
1 Unscrew the housing cover
2 Loosen compression nut of the cable entry
3 Remove approx. 10 cm of the cable mantle, strip approx.

1 cm insulation from the individual wires

4 Insert the cable into VEGABOX 01 through the cable entry
5 Loosen the screw terminals with a screwdriver
6 Insert the wire ends into the open terminals according to

the wiring plan

7 Tighten screw terminals again
8 Check the hold of the wires in the terminals by lightly

pulling on them

9 Connect the screen to the ground terminal
10 Connect the ground terminal outside on the housing

according to specification (low impedance)

11 Tighten the compression nut of the cable entry. The seal

ring must completely encircle the cable

12 Screw the housing cover back on
The electrical connection is finished.

Select connection

cable for Ex applica-

tions

Cable screening and ground-

ing

Cable screen and grounding

for Ex applications

10

VEGABOX 01

Connecting to voltage supply

32771

-EN
-061121