VEGA VEGAFLEX 66 (-20…+250°C) 4 … 20 mA_HART two-wire User Manual

Page 49

Advertising
background image

2

4

3

1

2

4

5

3

1

5

Fig. 23: Measuring ranges of the VEGAFLEX 66 - rod and cable version

1

Reference plane

2

Probe length

3

Measuring range (default setting refers to the measuring range in water)

4

Upper dead band (see diagrams under Accuracy - grey section)

5

Lower dead band (see diagrams under Accuracy - grey section)

Output variable

O

utput signal

4 … 20

mA/HART

C

ycle time

min. 1 s (dependent on the parameter setting)

S

ignal resolution

1.6 µA

F

ailure signal current output (adjustable)

mA value unchanged 20.5 mA, 22 mA, < 3.6 mA
(

adjustable)

M

ax. output current

22

mA

L

oad

see load diagram under Power supply

D

amping (63 % of the input variable)

0 … 999

s, adjustable

F

ulfilled NAMUR recommendations

NE

43

HART

output values

-

1. HART

value (Primary Value)

D

istance to the level

VEGAFLEX

66 • 4 … 20

mA/HART two-wire

49

10 S

upplement

34169

-

EN

-100426