6 Dismounting

6.1 Dismounting procedure

Note chapter "Mounting" and carry out the stated steps in

reverse order.

Warning:

If you want to remove the lock fitting for service or control

purposes, make sure that the vessel is unpressurised.

If you proceed as follows, it is not necessary to readjust the

switching point and the lock fittings must not be dismounted

completely.
1 Switch off power supply of the sensor
2 Remove all connection cables
3 Loosen the mounting boss with a screwdriver
4 Remove the sensor together with the lock fitting

6.2 Disposal

The ARV-WE63.2 consists of materials which can be recycled

by specialised recycling companies. Mark the instrument as

scrap and dispose it according to the legal national regu-

lations.
Materials: see "Technical data"
If you cannot dispose of the instrument properly, please

contact us about disposal methods or return.

Lock fitting ARV-WE63.2 - - pressure range: -1 … 16 bar

11

Dismounting

32360

-EN

-060822