VEGA VEGAFLEX 66 (-200…+400°C) 4 … 20 mA_HART four-wire User Manual

Page 46

Advertising
background image

2

4

3

5

1

2

4

5

3

1

Fig. 18: Measuring ranges of the VEGAFLEX 66 - rod and cable version

1

Reference plane

2

Probe length

3

Measuring range

4

Upper dead band (see diagrams under Accuracy - grey section)

5

Lower dead band (see diagrams under Accuracy - grey section)

Output variable

O

utput signal

4 … 20

mA/HART (active)

C

ycle time

min. 1 s (dependent on the parameter setting)

S

ignal resolution

1.6 µA

F

ailure signal current output (adjustable)

mA value unchanged 20.5 mA, 22 mA, < 3.6 mA
(

adjustable)

M

ax. output current

22

mA

46

VEGAFLEX

66 • 4 … 20

mA/HART four-wire

10 S

upplement

34174

-EN

-100426

Advertising