5 setup, 1 setup, 5 s etup – VEGA CAP E31R User Manual
Page 9
5 S
etup
5
.1 Setup
Proceed as follows for a fresh adjustment:
3
4
5
6
1
2
Fig. 1: Oscillator with relay output
1
Type label
2
Connection terminals
3
Tensile proving ring
4
Control lamp
5
DIL switch for mode adjustment
6
Potentiometer for switching point adaptation
1
Make sure that the probe is uncovered.
2
Pierce the cover of the potentiometer (6) with a screw-
driver.
3
Turn the below potentiometer (6) first of all anticlockwise
(max. 20 turns) until the control lamp signals "covered".
Mode A (overfill protection) = control lamp lights
Mode B (dry run protection) = control lamp extinguishes
If this condition is already reached, you can continue with
the next step.
4
Turn the potentiometer (6) very slowly (due to the damping)
clockwise until the control lamp signals "uncovered".
Mode A (overfill protection) = control lamp extinguishes
Mode B (dry run protection) = control lamp lights
Fresh adjustment
Electronics module - CAP E31R
9
Setup