5 S

etup

5

.1 Setup

Proceed as follows for a fresh adjustment:

3

4

5

6

1

2

Fig. 1: Oscillator with relay output
1

Type label

2

Connection terminals

3

Tensile proving ring

4

Control lamp

5

DIL switch for mode adjustment

6

Potentiometer for switching point adaptation

1

Make sure that the probe is uncovered.

2

Pierce the cover of the potentiometer (6) with a screw-
driver.

3

Turn the below potentiometer (6) first of all anticlockwise
(max. 20 turns) until the control lamp signals "covered".

Mode A (overfill protection) = control lamp lights
Mode B (dry run protection) = control lamp extinguishes

If this condition is already reached, you can continue with
the next step.

4

Turn the potentiometer (6) very slowly (due to the damping)
clockwise until the control lamp signals "uncovered".

Mode A (overfill protection) = control lamp extinguishes
Mode B (dry run protection) = control lamp lights

Fresh adjustment