9 Supplement

VEGACAP 67 • - contactless electronic switch

31314-EN-130916

Ʋ Single chamber housing

– 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),

1 x blind plug M20 x 1.5; attached 1 x cable entry

M20 x 1.5

or:

– 1 x cable entry ½ NPT, 1 x blind plug ½ NPT, 1 x cable

entry ½ NPT

or:

– 1 x plug M12 x 1; 1 x blind plug M20 x 1.5

Spring-loaded terminals

for wire cross-section up to 1.5 mm² (AWG 16)

Adjustment elements
Mode switch

Ʋ Min.

Min. detection or dry run protection

Ʋ Max.

Max. detection or overflow protection

DIL switch for measuring range selection

Ʋ range 1

0 … 20 pF

Ʋ range 2

0 … 85 pF

Ʋ range 3

0 … 450 pF

Potentiometer

Switching point adaptation

Voltage supply
Operating voltage

20 … 253 V AC, 50/60 Hz, 20 … 253 V DC

Domestic current requirement

approximately 3 mA (via load circuit)

Load current

Ʋ Min.

10 mA

Ʋ Max.

400 mA (at I > 300 mA the ambient temperature can be

max. 60 °C/140 °F) max. 4 A up to 40 ms

Electrical protective measures
Protection rating

IP 66/IP 67

Overvoltage category

III

Protection class

I