5

Connecting to power supply

5

.1 Preparing the connection

Always keep in mind the following safety instructions:

l

Connect only in the complete absence of line voltage

l

If overvoltage surges are expected, overvoltage arresters should
be installed according to Foundation Fieldbus specification.

Tip:
We recommend VEGA overvoltage arrester B63-32.

In hazardous areas you should take note of the appropriate regulations,
conformity and type approval certificates of the sensors and power
supply units.

The instrument requires a operating voltage of 9 … 32 V DC.
Operating voltage and the digital bus signal are carried on the same
two-wire connection cable. Power is supplied via the H1 power supply.

Connection is carried out with screened cable according to Fieldbus
specification.

Use cable with round cross-section. A cable outer diameter of 5 … 9 mm
(0.2 … 0.35 in) ensures the seal effect of the cable gland. If you are
using cable with a different diameter or cross-section, exchange the
seal or use a suitable cable gland.

Make sure that the entire installation is carried out according to the
Fieldbus specification. In particular, make sure that the termination of
the bus is done with appropriate terminating resistors.

On the instrument with cable entry ½ NPT and plastic housing there is
a metallic ½" threaded insert moulded into the plastic housing.

Caution:
No grease should be used when screwing the NPT cable gland or
steel tube into the threaded insert. Standard grease can contain
additives that corrode the connection between threaded insert and
housing. This would influence the stability of the connection and the
tightness of the housing.

In systems with potential equalisation, connect the cable screen
directly to ground potential at the power supply unit, in the connection
box and at the sensor. The screen in the sensor must be connected
directly to the internal ground terminal. The ground terminal outside on
the housing must be connected to the potential equalisation (low
impedance).

Safety instructions

Voltage supply

Connection cable

Cable gland ½ NPT

Cable screening and
grounding

VEGAFLEX

61 • Foundation Fieldbus

17

5 Connecting to power supply

31836

-

EN