epending on the tube diameter or tube length, one or several spacers
can be mounted. With cable probes, the cable can also be strained to
avoid contact with the tube.
K
eep in mind that buildup can form on the spacers. Strong buildup can
influence the measurement.
M
icrowaves can penetrate plastics. For process technical reasons,
plastic standpipes are problematic. If durability is no problem, then we
recommend the use of metal standpipes.
1
Fig. 5: Position of the spacer
1
Spacer
Note:
M
easurement in a standpipe is not recommended for very adhesive
products.
M
ake sure that the probe is not subjected to strong lateral forces.
M
ount VEGAFLEX 63 at a position in the vessel where no
disturbances, e.g. from filling openings, agitators, etc., can occur.