3 function chart – VEGA VEGAWAVE 61 - transistor (NPN-PNP) User Manual

Page 20

Advertising
background image

By default, the potentiometer of VEGAWAVE 61 is set to the right stop
(> 0.02 g/cm³ or 0.0008 lbs/in³). In case of very light-weight solids, turn
the potentiometer to the left stop (> 0.008 g/cm³ or 0.0003 lbs/in³).
VEGAWAVE

61 will thus be more sensitive and can detect light-weight

solids more reliably.

For instruments detecting solids in water, these settings are not
applicable. The switching point adaptation is preset and must not be
changed.

With the mode switch (min./max.) you can change the switching status
of the transistor output. You can set the required mode according to
the "Function chart" (max. - max. detection or overflow protection, min.
- min. detection or dry run protection).

We recommend connecting according to the quiescent current
principle (switching output is opened when the switching point is
reached) because the transistor output takes on the same (safe)
condition if a failure is detected.

Control lamp for indication of the switching status

l

Green = Output closed

l

Red = Output open

l

red (flashing) = failure

6

.3 Function chart

The following chart provides an overview of the switching conditions
depending on the adjusted mode and level.

Level

Switching status Control lamp

Mode max.
Overflow protec-
tion

closed

Green

Mode max.
Overflow protec-
tion

open

Red

Mode min.
Dry run protection

closed

Green

Mode min.
Dry run protection

open

Red

Mode adjustment (2)

Signal lamp (5)

20

VEGAWAVE

61 • - transistor (NPN/PNP)

6 Set up

32248

-EN

-120418

Advertising