4 recurring function test – VEGA VEGAVIB 62 - NAMUR User Manual

Page 20

Advertising
background image

Level

Signal current -
Sensor

Control lamp

Falling characteris-
tics max.

2.4 mA

Falling characteris-
tics max.

1 mA

Rising characteris-
tics min.

2.4 mA

Rising characteris-
tics min.

1 mA

Malfunction

any

1 mA

flashes

6

.4 Recurring function test

According to IEC 61508.

VEGAVIB

62 is qualified in mode A (overfill protection) for use in

measuring chains of stage SIL2 according to IEC 61508 (redundant,
stage SIL3).

The following instrument combinations meet the requirements
according to SIL:

VEGAVIB

62

l

Oscillator VB60N

The recurring test according to IEC 61508 can be carried out by
pushing the simulation key on the electronics module or by briefly (> 2
seconds) interrupting the cable to the sensor. The correct sequence of
the switching conditions must be monitored via the switching amplifier
as well as the connected systems. The sensor must neither be
removed nor response must be triggered by filling the vessel. This
applies to VEGAVIB 62 with NAMUR electronics module VB60N.

SIL

Recurring function test

20

VEGAVIB

62 • - NAMUR

6 Set up

31216

-EN

-120418

Advertising