VEGA VEGAWAVE 62 - contactless electronic switch User Manual

Page 17

Advertising
background image

1

4

4

4

2

3

Fig. 9: Material versions, single chamber housing

1

Plastic (not with EEx d)

2

Aluminium

3

Stainless steel (not with EEx d)

4

Filter element for pressure compensation (not with EEx d)

We recommend connecting VEGAWAVE 62 in such a way that the
switching circuit is open when there is a level signal, line break or
failure (safe condition).

The contactless electronic switch is always shown in non-operative
condition.

Warning:
The instrument must not be operated without an intermediately
connected load, because the electronics would be destroyed if
connected directly to the mains. It is not suitable for connection to low
voltage PLC inputs.

Examples for typical applications:

l

Load resistance at 24 V DC: 88 … 1800 Ω

l

Rated power, relay 253 V AC: > 2.5 VA

l

Rated power, relay 24 V AC: > 0.5 VA

For direct control of relays, contactors, magnet valves, warning lights,
horns etc.

Domestic current is temporarily lowered below 1 mA after switching off
the load so that contactors, whose holding current is lower than the
constant domestic current of the electronics, are reliably switched off.

Housing overview

Wiring plan

VEGAWAVE

62 • - contactless electronic switch

17

5 Connecting to power supply