3 wiring plan, single chamber housing – VEGA VEGAFLEX 67 (-20…+250°C) 4 … 20 mA_HART two-wire User Manual

Page 17

Advertising
background image

2

I

f an indicating and adjustment module is installed, remove it by

turning it to the left.

3

L

oosen compression nut of the cable entry

4

R

emove approx. 10 cm (4 in) of the cable mantle, strip approx.

1

cm (0.4 in) of insulation from the ends of the individual wires

5

I

nsert the cable into the sensor through the cable entry

6

L

ift the opening levers of the terminals with a screwdriver (see

following illustration)

7

I

nsert the wire ends into the open terminals according to the wiring

plan

Fig. 7: Connection steps 6 and 7

8

P

ress down the opening levers of the terminals, you will hear the

terminal spring closing

9

C

heck the hold of the wires in the terminals by lightly pulling on

them

10 C

onnect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation

11 T

ighten the compression nut of the cable entry. The seal ring must

completely encircle the cable

12 S

crew the housing cover back on

T

he electrical connection is finished.

5

.3 Wiring plan, single chamber housing

T

he following illustrations apply to the non-Ex as well as to the Ex-ia

version.

VEGAFLEX

67 • 4 … 20

mA/HART - two-wire

17

5 C

onnecting to power supply

32307

-

EN

-120329