VEGA VEGAFLEX 63 4 … 20 mA_HART two-wire User Manual

Page 46

Advertising
background image

2

4

5

3

1

2

4

5

3

1

Fig. 22: Measuring ranges of VEGAFLEX 63

1

Reference plane

2

Probe length

3

Measuring range (default setting refers to the measuring range in water)

4

Upper dead band (see diagrams under Accuracy - grey section)

5

Lower dead band (see diagrams under Accuracy - grey section)

Output variable

O

utput signal

4 … 20

mA/HART

C

ycle time

min. 1 s (dependent on the parameter setting)

S

ignal resolution

1.6 µA

F

ailure signal current output (adjustable)

mA value unchanged 20.5 mA, 22 mA, < 3.6 mA
(

adjustable)

M

ax. output current

22

mA

L

oad

see load diagram under Power supply

D

amping (63 % of the input variable)

0 … 999

s, adjustable

F

ulfilled NAMUR recommendations

NE

43

HART

output values

-

1. HART

value (Primary Value)

D

istance to the level

-

2. HART

value (Secondary Value)

D

istance to the level - scaled (for example hl, %)

R

esolution, digital

>

1

mm (0.039 in)

46

VEGAFLEX

63 • 4 … 20

mA/HART two-wire

10 S

upplement

31841

-EN

-100426

Advertising