Transistor output
For connection to binary inputs of a PLC with an
input resistance < 100 kΩ.

If the input of the PLC is high-impedance, you have
to connect a load resistor (R

L

)

with 100 kΩ

according to the following illustrations in parallel to
the input of the PLC.

For the plug version valve plug ISO 4400, standard
cable with round wire cross-section can be used.
Cable diameter 4.5 … 7 mm, protection IP 65.

The M12 x 1 plug connection requires a complete
confectioned cable with plug.

3

2

1

3

2

1

L-

L+

R

L

PA

R

L

L-

L+

PA

1

2

Fig. 17: Wiring plan, Transistor output with valve plug ISO 4400

1

Max. level detection

2

Min. level detection

P

A

Potential equalisation

R

L

Load resistor (contactor, relay etc. or external resistor 100 kΩ)

R

L

R

L

1

4

2

3

1

4

2

3

-

Max.

Min.

-

+

+

Fig. 18: Wiring plan (housing), transistor output with M12 x 1 plug
connection

1

Brown

2

White

3

Blue

4

Black

R

L

Load resistor (contactor, relay etc. or external resistor 100 kΩ)

VEGASWING S 51

17

Connecting to power supply

32947

-