6 Setup
VEGACAP 67 • - two-wire
31317-EN-130916
change the sensitivity of the probe to the electrical properties of the
product and the conditions in the vessel. This is necessary so that the
level switch can also reliably detect products e.g. with very low or very
high dielectric figure.
range 1: 0 … 20 pF
Range 2: 0 … 85 pF
Range 3: 0 … 450 pF
Control lamp for indication of the device status.
•
green = instrument functions
•
red (flashing) = failure
See operating instructions manual of the "Signal conditioning instru-
ment".
The adjustment of the switching point is only possible in installed
condition.
The detailed adjustment of VEGACAP 67 is described in the operat-
ing instructions manual of the "Signal conditioning instrument".
Signal lamp (4)
Switching point adjust-
ment