3 function chart – VEGA VEGAVIB 55 - NAMUR User Manual

Page 19

Advertising
background image

The NAMUR output can be switched over to falling or rising

characteristics (see also "Function chart").

The simulation key is located in a recess on the upper side of

the oscillator. Push the simulation key with a suitable object

(screwdriver, pen, etc.).
When the key is pushed, a line break between sensor and

processing unit is simulated. The signal lamp on the sensor

extinguishes. The measuring system must signal a fault and

take on a safe condition when the key is pushed.
Keep in mind that the connected instruments will be activated

during operation. This allows you to check the correct function

of the measuring system.

Control lamp (LED) for indication of the switching status.

l

yellow = High current >=2.2 mA

l

dark = Low current <=1 mA

l

yellow (flashing) = Failure <=1 mA

6.3 Function chart

VEGAVIB 55 level switch

The following chart provides an overview of the switching

conditions depending on the adjusted mode and level.

Note:

The mode setting on the NAMUR amplifier must be selected in

such a way that the switching output takes on safe condition in

case of failure (I <=1 mA).

Level

Signal current -

Sensor

Control lamp

Falling characteris-

tics max.

>=2.2 mA

Falling characteris-

tics max.

<=1 mA

Simulation key (2)

Signal lamp (5)

VEGAVIB 55 - - NAMUR

19

Setup

31214

-EN

-070109