Technical data kfd2-sr2-ex1.w – VEGA KFD2-SR2-Ex1.W User Manual

Page 2

Advertising
background image

2

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

Technical Data

KFD2-SR2-Ex1.W

103

36

7_

EN

G.xm

l

2

003

-03-

2

5

Supply

Connection

Power Rail or terminals 14+, 15-

Rated voltage

20 ... 30 V DC

Ripple

≤ 10 %

Rated current

20 ... 23 mA

Input

Connection

terminals 1+, 2+, 3-

Rated values

acc. to IEC 60947-5-6 (NAMUR, DIN 19234), see system description for electrical data

Open circuit voltage/Short-circuit current

approx. 8 V DC / approx. 8 mA

Switching point/Switching hysteresis

1,2 ... 2,1 mA / approx. 0,2 mA

Pulse / Pause ratio

≥ 20 ms / ≥ 20 ms

Lead monitoring

breakage I

≤ 0,1 mA , short-circuit I > 6 mA

Output

Connection

terminals 7, 8, 9

Output

signal ; relay

Contact loading

253 V AC / 2 A / cos

ϕ > 0.7; 126.5 V AC / 4 A / cos ϕ > 0.7; 40 V DC / 2 A resistive load

Energised/De-energised delay

approx. 20 ms / approx. 20 ms

Mechanical life

10

7

switching cycles

Transfer characteristics

Switching frequency

< 10 Hz

Electrical isolation

Output/Power supply

reinforced insulation according to IEC 61140, rated insulation voltage 300 V

eff

Standard conformity

Climatic conditions

acc. to DIN IEC 721

Directive conformity

Electromagnetic compatibility

standards

Directive 89/336/EG

EN 61326, EN 50081-2, NE 21

Ambient conditions

Ambient temperature

-20 ... 60 °C (253 ... 333 K)

Mechanical specifications

Protection degree

IP20

Mass

approx. 150 g

Data for application in conjunction
with hazardous areas

EC-Type Examination Certificate

PTB 00 ATEX 2080 , for additional certificates see www.pepperl-fuchs.com

Group, category, type of protection

¬ II (1) G D [EEx ia] IIC [circuit(s) in zone 0/1/2]

Input

EEx ia IIC

Voltage

U

0

10,5 V

Current

I

0

13 mA

Power

P

0

34 mW (linear characteristic)

Type of protection [EEx ia and EEx ib]

Explosion group

IIA

IIB

IIC

External capacitance

75

µF

16,8

µF

2,41

µF

External inductance

1 H

840 mH

210 mH

Statement of conformity

TÜV 99 ATEX 1493 X , observe statement of conformity

Group, category, type of protection,
Temperature classification

¬ II 3 G EEx nAC IIC T4 [device in zone 2]

Supply

Safety maximum voltage U

m

253 V AC / 125 V DC (Attention! U

m

is no rated voltage.)

Output

Contact loading

253 V AC / 2 A / cos

ϕ > 0.7; 126.5 V AC / 4 A / cos ϕ > 0.7; 40 V DC / 2 A resistive load (PTB 00 ATEX 2080)

50 V AC / 4 A / cos

ϕ > 0.7; 40 V DC / 2 A resistive load (TÜV 99 ATEX 1493 X)

Safety maximum voltage U

m

253 V AC (Attention! The rated voltage can be lower)

Electrical isolation

Input/Output

safe electrical isolation acc. to EN 50020, voltage peak value 375 V

Input/Power supply

safe electrical isolation acc. to EN 50020, voltage peak value 375 V

Directive conformity

standards

Directive 94/9 EU

EN 50014, EN 50020, EN 50021

Entity parameter

Certification number

J.I.3002773

FM control drawing

No. 116-0035

Suitable for installation in division 2

yes

Connection

terminals 1, 3; 2, 3; 4, 6; 5, 6

Input

I

Voltage V

OC

12,9 V

Current I

t

19,8 mA

Advertising