VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual
Page 64
64
11 Supplement
VEGAPULS 62 • Profibus PA
36505-EN-121011
Input variable
Measured variable
The measured quantity is the distance between process
fitting of the sensor and product surface. The reference
plane is the seal surface on the hexagon or the lower
side of the flange.
3
4
2
1
Fig. 55: Data of the input variable
1 Reference plane
2 Measured variable, max. measuring range
3 Antenna length
4 Useful measuring range
Standard electronics
Max. measuring range
35 m (114.83 ft)
Recommended measuring range
Ʋ Antenna ø 40 mm (1.575 in)
up to 15 m (49.21 ft)
Ʋ Antenna ø 48 mm (1.89 in)
up to 20 m (65.62 ft)
Ʋ Antenna ø 75 mm (2.953 in), ø 95 mm
(3.74 in), parabolic antenna
up to 35 m (114.83 ft)
Electronics with increased sensitivity
Max. measuring range
75 m (246.1 ft)
Recommended measuring range
Ʋ Antenna ø 40 mm (1.575 in)
up to 15 m (49.21 ft)
Ʋ Antenna ø 48 mm (1.89 in)
up to 20 m (65.62 ft)
Ʋ Antenna ø 75 mm (2.953 in)
up to 40 m (131.23 ft)
Ʋ Antenna ø 95 mm (3.74 in)
up to 50 m (164 ft)
Ʋ Parabolic antenna
up to 75 m (246.1 ft)
Output variable
Output signal
digital output signal, format according to IEEE-754
Sensor address
126 (default setting)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Profibus PA profile
3.02