Power feed modules KFD2-EB2...

The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
can supply up to 100 individual devices depending on the power consumption of the devices. A galvanically isolated mechanical
contact uses the Power Rail to transmit collective error messages.

Power Rail UPR-03

The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an aluminium profile rail 35 mm x 15 mm. To
make electrical contact, the devices are simply engaged.

The Power Rail must not be fed via the device terminals of the individual devices!

Configuration

7

8

9

10

11

12

1

2

3

4

5

6

13

14

15

1

2

PWR

CHK

OUT

S1
S2
S3

123

123

S1

S3

II

S2

I

Switch position

Operating status

Factory settings: switch 1, 2 and 3 in position I

S

Function

Position

1

Mode of operation

Channel I (relay)

energized

with high input current

I

with low input current

II

2

Mode of operation

Channel II (relay)

energized

with high input current

I

with low input current

II

3

Line fault detection

ON

I

OFF

II

Control circuit

Input signal

Initiator high impedance/

contact opened

low input current

Initiator low impedance/

contact closed

high input current

Lead breakage,

lead short-circuit

Line fault