6 Set up with the display and adjustment module PLICSCOM

VEGABAR 53 • 4 … 20 mA/HART

36722-EN-130321

Caution:

Note the following if the VEGABAR 53 with corresponding approval is

used as part of an overfill protection system according to WHG (Water

Resources Act):
If a linearization curve is selected, the measuring signal is no longer

linearly proportional to the level. This must be taken into consideration

by the user, particularly when setting the switching point on the limit

signal indicator.

This function enables reading out parameter adjustment data as well

as writing parameter adjustment data into the sensor via the display

and adjustment module. A description of the function is available in

the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:

Measured value presentation

Adjustment

Damping

Linearization curve

Sensor-TAG

Displayed value

Display unit

Scaling

Current output

Unit of measurement

Language

The following safety-relevant data are not read out or written:

SIL

HART mode

6)

PIN

Application

Copy sensor data

Copy sensor data?

Basic adjustment

The reset function resets all parameters adjusted by the user to the

delivery status and the peak values to the actual values.

Reset

Select reset?

Reset
Basic adjustment
Peak value, measured value
Peak value, temperature

Copy sensor data

Reset

6)

With instruments with signal output 4 … 20 mA/HART