VEGA VEGABAR 51 Profibus PA User Manual

Page 54

Advertising
background image

54

10 Supplement

VEGABAR 51 • Profibus PA

36714-EN-130321

Display and adjustment module
Voltage supply and data transmission

through the sensor

Indication

LC display in dot matrix

Adjustment elements

4 keys

Protection rating

Ʋ unassembled

IP 20

Ʋ mounted into the sensor without cover IP 40

Material

Ʋ Housing

ABS

Ʋ Inspection window

Polyester foil

Voltage supply
Operating voltage

Ʋ Non-Ex instrument

9 … 32 V DC

Ʋ Ex-ia instrument

9 … 24 V DC

Ʋ Exd instrument

14 … 32 V DC

Operating voltage with illuminated display and adjustment module

Ʋ Non-Ex instrument

18 … 32 V DC

Ʋ Ex-ia instrument

18 … 24 V DC

Ʋ Exd instrument

18 … 32 V DC

Max. number of sensors on the DP/PA

segment coupler non-Ex/Ex

32/10

Electrical protective measures
Protection rating

Ʋ Housing, standard

IP 66/IP 67

17)

Ʋ Aluminium and stainless housing

(optionally available)

IP 68 (1 bar)

18)

Ʋ Process component in IP 68 version IP 68 (25 bar)

Ʋ External housing

IP 65, IP 66/IP 68 (0.2 bar)

Overvoltage category

III

Protection class

II

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully

noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"

and "serial number search" as well as via "Downloads" and "Approvals".

17)

Instruments with gauge pressure measuring ranges cannot detect the ambient pressure when submerged, e.g.

in water. This can lead to falsification of the measured value.

18)

Only with instruments with absolute pressure ranges.

Advertising