5 Connecting to power supply

VEGABAR 66 • 4 … 20 mA/HART - climate compensated

36738-EN-130321

8. Press down the opening levers of the terminals, you will hear the

terminal spring closing

9. Check the hold of the wires in the terminals by lightly pulling on

them

10. Connect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation

11. Tighten the compression nut of the cable entry. The seal ring must

completely encircle the cable

12. Screw the housing cover back on
The electrical connection is hence finished.

Fig. 12: Connection steps 6 and 7

Proceed as follows:
1. Loosen the four screws on the housing base with an Allen key

size 4

2. Remove the mounting plate from the housing socket

IP 68 version with exter-

nal housing