VEGA VEGABAR 53 Foundation Fieldbus User Manual

Page 46

Advertising
background image

46

10 Supplement

VEGABAR 53 • Foundation Fieldbus

36724-EN-130321

Ʋ Ground terminal

316Ti/316L

Ʋ Ohmic contact

Between ground terminal and process fitting

Ʋ Connection cable between transmitter

and external electronics housing with

IP 68 version

PUR

Ʋ Type label support on connection

cable

PE hard

Ʋ Connection cable with IP 68 1 bar

version

PE, PUR

Weight approx.

0.8 kg (1.764 lbs)

Output variable
Output

Ʋ Signal

digital output signal, Foundation Fieldbus protocol

Ʋ Physical layer

according to IEC 61158-2

Channel Numbers

Ʋ Channel 1

Primary value

Ʋ Channel 2

Secondary value 1

Ʋ Channel 3

Secondary value 2

Ʋ Channel 4

Temperature value

Transmission rate

31.25 Kbit/s

Current value

10 mA, ±0.5 mA

Dynamic behaviour output
Run-up time approx.

10 s

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 26: Sudden change of the process variable. t

T

: dead time; t

A

: rise time; t

S

: jump response time

1 Process variable

2 Output signal

Dead time

≤ 150 ms

Rise time

≤ 100 ms (10 … 90 %)

Step response time

≤ 250 ms (ti: 0 s, 10 … 90 %)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Advertising