VEGA VEGABAR 52 Profibus PA - climate compensated User Manual

Page 49

Advertising
background image

49

10 Supplement

VEGABAR 52 • Profibus PA - climate compensated

36788-EN-130321

Adjustment range of the min./max. adjustment relating to the nominal measuring range:

Ʋ Percentage value

-10 … 110 %

Ʋ Pressure value

-20 … 120 %

Adjustment range of the zero/span adjustment relating to the nominal measuring range:

Ʋ zero

-20 … +95 %

Ʋ Span

-120 … +120 %

10)

Ʋ Difference between zero and span

max. 120 % of the nominal range

Recommended max. turn down

5 : 1 (no limitation)

Nominal measuring ranges and overload capability in bar/kPa
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-

terial and version of the process fitting are possible. The specifications on the nameplate apply.

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

Gauge pressure
0 … +0.2 bar/0 … +20 kPa

+35 bar/+3500 kPa

-1 bar/-100 kPa

0 … +0.4 bar/0 … +40 kPa

+50 bar/+5000 kPa

-1 bar/-100 kPa

0 … +1 bar/0 … +100 kPa

+50 bar/+5000 kPa

-1 bar/-100 kPa

0 … +2.5 bar/0 … +250 kPa

+50 bar/+5000 kPa

-1 bar/-100 kPa

0 … +5 bar/0 … +500 kPa

+65 bar/+6500 kPa

-1 bar/-100 kPa

0 … +10 bar/0 … +1000 kPa

+90 bar/+9000 kPa

-1 bar/-100 kPa

0 … +25 bar/0 … +2500 kPa

+130 bar/+13000 kPa

-1 bar/-100 kPa

0 … +60 bar/0 … +6000 kPa

+200 bar/+20000 kPa

-1 bar/-100 kPa

-1 … 0 bar/-100 … 0 kPa

+35 bar/+3500 kPa

-1 bar/-100 kPa

-1 … +1.5 bar/-100 … +150 kPa

+50 bar/+5000 kPa

-1 bar/-100 kPa

-1 … +5 bar/-100 … +500 kPa

+65 bar/+6500 kPa

-1 bar/-100 kPa

-1 … +10 bar/-100 … +1000 kPa

+90 bar/+9000 kPa

-1 bar/-100 kPa

-1 … +25 bar/-100 … +2500 kPa

+130 bar/+13000 kPa

-1 bar/-100 kPa

-1 … +60 bar/-100 … +6000 kPa

+200 bar/+20000 kPa

-1 bar/-100 kPa

-0.1 … +0.1 bar/-10 … +10 kPa

+35 bar/+3500 kPa

-1 bar/-100 kPa

-0.2 … +0.2 bar/-20 … +20 kPa

+35 bar/+3500 kPa

-1 bar/-100 kPa

-0.5 … +0.5 bar/-50 … +50 kPa

+50 bar/+5000 kPa

-1 bar/-100 kPa

Nominal measuring ranges and overload capability in psig
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-

terial and version of the process fitting are possible. The specifications on the nameplate apply.

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

Gauge pressure
0 … +3 psig

+500 psig

-15 psig

10)

Values less than -1 bar cannot be set.

Advertising