VEGA KFA6-SR2-Ex1.W User Manual

Kfa6-sr2-ex1.w isolated switch amplifiers, Composition

Advertising
background image

1

103

37

4_

EN

G.xm

l

2

003

-03-

2

5

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

KFA6-SR2-Ex1.W

Isolated switch amplifiers

yellow

green

Output

Power

supply

Saf

e area

Input I EEx ia IIC

Switch S3 in position I

Switch S3 in position I

Switch S3 in position I

Switch S3 in position II

Hazar

dous area

LB

SC

red

Power

Rail

LB/SC
collective
error message

only
KFD2-SR2-Ex1.W

without LB, SC

without SC

&

3-

1+

7

8

9

S1

14 15

+

+

-

2+

II

I

1+

3-

1+

3-

3-

2+

3-

1+

10 k

10 k

400

Ω ≤ R ≤ 2 kΩ

S3

-

Composition

230 V AC
• 1-channel

• Control circuit EEx ia IIC

• Reversible mode of operation

• 1 relay output with 1 changeover

contact

• EMC acc. to NAMUR NE 21

• LB/SC monitoring

• Usable up to SIL 2 acc. to IEC 61508

The transformer isolated barrier
transfers digital signals from the
hazardous area. Sensors per
DIN EN 60947-5-6 (NAMUR) and
mechanical contacts may be used as
alarms. Control circuits are monitored
for lead breakage (LB) and short circuit
(SC). The external faults are indicated
according to NAMUR NE44 by a red
flashing LED. For type KFD2-SR2-
Ex1.W, an LB/SC collective error
message is in addition transferred
through the Power Rail to the power
feed module. The intrinsically safe input
is per DIN EN 50020 safely isolated
from the output and the power supply.
The relay output is in accordance with
IEC 61140 safely isolated from the
power supply.

Function

Output: relay

Advertising