Technical Data

KFD0-CS-Ex1.51P

071

98

4_

EN

G.xm

l

2

003

-03-

2

4

Supply

Power loss

0,2 W

Inputs/Outputs (not intrinsically safe)

Connection

terminals 12-, 11+; 8-, 10-, 9+

Voltage

4 ... 35 V DC

Safety maximum voltage U

m

-

Current

0 ... 40 mA

Power loss

at 40 mA and U

in

< 24 V: 700 mW per channel

at 40 mA and UE > 24 V: 1.2 W per channel

Inputs/Outputs (Intrinsically safe)

Connection

terminals 1+, 2-; 4+, 5-

Output voltage

for 4 V < U

in

< 24 V:

≥ U

in

- (0.4 x current in mA) - 1

for U

in

> 24 V:

≥ 23 V - (0.4 x current in mA)

Short-circuit current

at U

in

> 24 V:

≤ 65 mA

Transfer current

≤ 40 mA

Transfer characteristics

Deviation

After calibration

≤ ± 200 µA; incl. calibration, linearity, hysteresis and load fluctuations at the output up to a load of 1 kOhm at
20 °C (293 K)

Temperature

< 2

µA/K (0 °C ... +50 °C); < 5 µA/K (-20 °C ... +60 °C)

Rise time

≤ 20 ms at 4 ... 20 mA and 250 Ohm load

Electrical isolation

Input/Output

safe electrical isolation acc. to EN 50020, voltage peak value 375 V

Standard conformity

Coordination of insulation

acc. to DIN EN 50178

Electrical isolation

acc. to DIN EN 50178

Electromagnetic compatibility

acc. to EN 50081-2 / EN 50082-2, NAMUR NE 21

Climatic conditions

acc. to DIN IEC 721

Directive conformity

Electromagnetic compatibility

standards

Directive 89/336/EG

on request

Ambient conditions

Ambient temperature

-20 ... 60 °C (253 ... 333 K)

Mechanical specifications

Protection degree

IP20

Mass

approx. 100 g

Data for application in conjunction
with hazardous areas

EC-Type Examination Certificate

BAS 98 ATEX 7343 ; for additional certificates see www.pepperl-fuchs.com

Group, category, type of protection

¬ II (1) G D [EEx ia] IIC (-20 °C

≤ T

a

≤ 60 °C)

Voltage

U

0

25,2 V

Current

I

0

93 mA

Power

P

0

585 mW

Type of protection [EEx ia]

Explosion group

IIA

IIB

IIC

External capacitance

75

µF

16,8

µF

2,41

µF

External inductance

32 mH

17 mH

4 mH

Statement of conformity

TÜV 99 ATEX 1499 X (observe statement of conformity)

Group, category, type of protection,
Temperature classification

¬ II 3 G EEx nA II T4

Electrical isolation

Input/Output

safe electrical isolation acc. to EN 50020, voltage peak value 375 V

Directive conformity

standards

Directive 94/9 EU

on request

Entity parameter

Certification number

4Z6A5.AX

FM control drawing

No. 116-0129

Suitable for installation in division 2

yes

Connection

terminals 2, 1

Input

I

Voltage V

OC

28,5 V

Current I

t

96 mA

Explosion group

A&B

C&E

D, F&G

Max. external capacitance C

a

0,13

µF

0,41

µF

1,09

µF

Max. external inductance L

a

3,93 mH 15,93 mH 32,21 mH

Safety parameter