Technical Data

KFD2-SR2-Ex2.W

103

36

8_

EN

G.xm

l

2

003

-06-

0

3

Supply

Connection

Power Rail or terminals 14+, 15-

Rated voltage

20 ... 30 V DC

Ripple

≤ 10 %

Rated current

≤ 50 mA

Power loss

0,7 W

Power consumption

< 1,3 W

Input

Connection

terminals 1+, 2+, 3-; 4+, 5+, 6-

Rated values

acc. to IEC 60947-5-6 (NAMUR, DIN 19234), see system description for electrical data

Open circuit voltage/Short-circuit current

approx. 8 V DC / approx. 8 mA

Switching point/Switching hysteresis

1,2 ... 2,1 mA / approx. 0,2 mA

Pulse/Pause ratio

≥ 20 ms / ≥ 20 ms

Lead monitoring

breakage I ≤ 0,1 mA , short-circuit I > 6 mA

Output

Connection

output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12

Output

I and II

signal ; relay

Contact loading

253 V AC / 2 A / cos ϕ > 0.7; 126.5 V AC / 4 A / cos ϕ > 0.7; 40 V DC / 2 A resistive load

Energised/De-energised delay

approx. 20 ms / approx. 20 ms

Mechanical life

10

7

switching cycles

Transfer characteristics

Switching frequency

≤ 10 Hz

Electrical isolation

Output/Power supply

reinforced insulation according to IEC 61140, rated insulation voltage 300 V

eff

Output/Output

from january 2002 reinforced insulation according to IEC 61140, rated insulation voltage 300 Veff

Standard conformity

Climatic conditions

acc. to DIN IEC 721

Directive conformity

Electromagnetic compatibility

standards

Directive 89/336/EG

EN 61326, EN 50081-2, NE 21

Ambient conditions

Ambient temperature

-20 ... 60 °C (253 ... 333 K)

Mechanical specifications

Protection degree

IP20

Mass

approx. 150 g

Data for application in conjunction
with hazardous areas

EC-Type Examination Certificate

PTB 00 ATEX 2080 , for additional certificates see www.pepperl-fuchs.com

Group, category, type of protection

¬ II (1) G D [EEx ia] IIC [circuit(s) in zone 0/1/2]

Input

EEx ia IIC

Voltage

U

0

10,5 V

Current

I

0

13 mA

Power

P

0

34 mW (linear characteristic)

Supply

Safety maximum voltage

U

m

253 V AC / 125 V DC (Attention! U

m

is no rated voltage.)

Type of protection [EEx ia and EEx ib]

Explosion group

IIA

IIB

IIC

External capacitance

75 µF

16,8

µF

2,41

µF

External inductance

1000 mH 840 mH

210 mH

Statement of conformity

TÜV 99 ATEX 1493 X , observe statement of conformity

Group, category, type of protection,
Temperature classification

¬ II 3 G EEx nAC IIC T4 [device in zone 2]

Output

Contact loading

253 V AC / 2 A / cos ϕ > 0.7; 126.5 V AC / 4 A / cos ϕ > 0.7; 40 V DC / 2 A resistive load (PTB 00 ATEX 2080)
50 V AC / 4 A / cos ϕ > 0.7; 40 V DC / 2 A resistive load (TÜV 99 ATEX 1493 X)

Safety maximum voltage

U

m

253 V AC (Attention! The rated voltage can be lower)

Electrical isolation

Input/Input

not available

Input/Output

safe electrical isolation acc. to EN 50020, voltage peak value 375 V

Input/Power supply

safe electrical isolation acc. to EN 50020, voltage peak value 375 V

Directive conformity

standards

Directive 94/9 EU

EN 50014, EN 50020, EN 50021

Entity parameter

Certification number

J.I.3002773

FM control drawing

No. 116-0035

Suitable for installation in division 2

yes

Advertising