4 Mounting

VEGAPULS 66 enamel • Foundation Fieldbus

36530-EN-121011

Fig. 8: Mounting of the radar sensor with inflowing medium

The socket piece should be dimensioned in such a way that the an-

tenna end protrudes at least 10 mm (0.4 in) out of the socket.

ca. 10 mm

Fig. 9: Recommended socket mounting

Align the sensor in liquids as vertical as possible to the product sur-

face to achieve an optimum measurement.

Fig. 10: Alignment in liquids

The mounting location of the radar sensor should be a place where no

other equipment or fixtures cross the path of the microwave signals.
Vessel installations, such as e.g. ladders, limit switches, heating spi-

rals, struts, etc., can cause false echoes and impair the useful echo.

Make sure when planning your measuring site that the radar sensor

has a "clear view" to the measured product.
In case of existing vessel installations, a false echo storage should be

carried out during setup.

Socket

Sensor orientation

Vessel installations