22

5 Connecting to power supply

VEGAPULS 66 enamel • 4 … 20 mA/HART - two-wire

36527-EN-121011

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should

be installed

Power supply and current signal are carried on the same two-wire

cable. The voltage supply range can differ depending on the instru-

ment version.
The data for power supply are specified in chapter "Technical data".
Provide a reliable separation between the supply circuit and the

mains circuits according to DIN VDE 0106 part 101.
Keep in mind the following additional factors that influence the operat-

ing voltage:

Output voltage of the power supply unit can be lower under nomi-

nal load (with a sensor current of 20.5 mA or 22 mA in case of fault

message)

Influence of additional instruments in the circuit (see load values in

chapter "Technical data")

The instrument is connected with standard two-wire cable without

screen. If electromagnetic interference is expected which is above the

test values of EN 61326-1 for industrial areas, screened cable should

be used.
For instruments with housing and cable gland, use cable with round

cross-section. A cable outer diameter of 5 … 9 mm (0.2 … 0.35 in)

ensures the seal effect of the cable gland. If you are using cable with

a different diameter, exchange the seal or use a suitable cable gland.
We generally recommend the use of screened cable for HART multi-

drop mode.

With plastic housing, the NPT cable gland or the Conduit steel tube

must be screwed without grease into the threaded insert.
Max. torque for all housings see chapter "Technical data"

If screened cable is necessary, connect the cable screen on both

ends to ground potential. In the sensor, the screen must be connected

directly to the internal ground terminal. The ground terminal on the

outside of the housing must be connected to the potential equalisa-

tion (low impedance).
If potential equalisation currents are expected, the connection on the

processing side must be made via a ceramic capacitor (e. g. 1 nF,

1500 V). The low frequency potential equalisation currents are thus

suppressed, but the protective effect against high frequency interfer-

ence signals remains.

Safety instructions

Voltage supply

Connection cable

Cable gland ½ NPT

Cable screening and

grounding