VEGA B62-36G User Manual
Page 11
Advertising
1
2
3
O
U
T
IN
IP
2
0
Fig. 6: Mounting in plastic housing
1
Overvoltage arrester
2
Pressure compensation
3
Ground terminal
The carrier rail inside the housing is galvanically connected to the
ground terminal outside on the housing. This ground terminal must be
connected (low impedance) with the potential equalization line (PA).
The wire cross-section must be at least 2.5 mm
2
, the cable must be as
short as possible.
Overvoltage arrester • B62-36G
11
3 Product description
40491
-
EN
-120329