VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) standpipe ver. Profibus PA User Manual
Page 47
47
11 Supplement
VEGAPULS 62 standpipe version • Profibus PA
36509-EN-121011
3
4
2
1
Fig. 27: Data of the input variable
1 Reference plane
2 Measured variable, max. measuring range
3 Antenna length
4 Useful measuring range
Max. measuring range
35 m (114.83 ft)
Useful measuring range
According to the respective standpipe length.
1)
Output variable
Output signal
digital output signal, format according to IEEE-754
Sensor address
126 (default setting)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Profibus PA profile
3.02
Number of FBs with AI (function blocks
with analogue input)
3
Default values
Ʋ 1. FB
PV
Ʋ 2. FB
SV 1
Ʋ 3. FB
SV 2
Current value
Ʋ Non-Ex and Ex ia instrument
10 mA, ±0.5 mA
Ʋ Ex-d instruments
16 mA, ±0.5 mA
Resolution, digital
< 1 mm (0.039 in)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
1)
Standpipe supply Ex factory up to 5.85 m (19.19 ft)