10 Supplement

VEGABAR 52 • Profibus PA

36719-EN-130321

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+15 … +25 °C (+59 … +77 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characterstic curve

Linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

< 0.2 mbar/20 Pa (0.003 psig)

Deviation determined according to the limit point method according to IEC 60770

5)

Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Deviation with absolutely flush process fittings EV, FT

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.05 %

Ʋ Turn down > 5 : 1

< 0.01 % x TD

Deviation with version 0.075 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.075 %

Ʋ Turn down > 5 : 1

< 0.015 % x TD

Deviation with version 0.1 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.1 %

Ʋ Turn down > 5 : 1

< 0.02 % x TD

Deviation with version 0.2 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.2 %

Ʋ Turn down > 5 : 1

< 0.04 % x TD

Deviation with absolute pressure measuring range 0.1 bar

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.25 %

Ʋ Turn down > 5 : 1

< 0.05 % x TD

Influence of the product or ambient temperature
Thermal change zero signal and output span
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Thermal change zero signal and output span, reference temperature 20 °C (68 °F):

Ʋ In the compensated temperature

range 0 … +100 °C (+32 … +212 °F)

< (0.05 % + 0.1 % x TD)

Ʋ Outside the compensated tempera-

ture range

< (0.05 % + 0.15 % x TD)

Thermal change zero signal and output span with absolute pressure measuring range 0.1 bar,

reference temperature 20 °C (68 °F):

5)

Incl. non-linearity, hysteresis and non-repeatability.