VEGA SOLITRAC 31 Foundation Fieldbus User Manual

Page 37

Advertising
background image

37

6 Set up with the display and adjustment module

SOLITRAC 31 • Foundation Fieldbus

41781-EN-131119

Menu

Menu item

Default value

Setup

Measurement loop name

Sensor

Isotope

Cs-137

Application

Level

Background radiation

0 ct/s

Unit of the process value

%

Temperature unit

° C

Adjustment min.

Min. process value = 0 %

Adjustment max.

Max. process value = 100 %

Linearization

0 ct/s = 100 %
90000 ct/s = 0 %

Damping

60 s

Real value correction

0

Mode

Overfill protection

Upper switching point - Pro-

cess value

0 %

Lower switching point - Pro-

cess value

0 %

Upper switching point - Tem-

perature

50 °C

Upper switching point - Tem-

perature

25 °C

Reference value - Relay

None

Block adjustment

Released

Address - Summation Slave free

Display

Language

Selected language

Displayed value

Pulse rate

Display unit

ct/s

Additional ad-

justments

Temperature unit

°C

Linearisation curve

Empty

HART mode

Standard
Address 0

With this function

Load parameter adjustment data from the sensor into the display

and adjustment module

Write parameter adjustment data from the display and adjustment

module into the sensor

This parameter is described in the operating instructions manual

"Display and adjustment module".

Additional adjustments -

Copy instrument settings