VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) HART - integrated accumulator User Manual
Page 61
61
11 Supplement
VEGAPULS 68 • HART - integrated accumulator
40935-EN-121011
Input variable
Measured variable
The measured quantity is the distance between process
fitting of the sensor and product surface. The reference
plane is the seal surface on the hexagon or the lower
side of the flange.
3
4
2
1
Fig. 46: Data of the input variable
1 Reference plane
2 Measured variable, max. measuring range
3 Antenna length
4 Useful measuring range
Max. measuring range
75 m (246.1 ft)
Recommended meas. range depending on the antenna diameter
Ʋ ø 40 mm (1.575 in)
up to 15 m (49.21 ft)
Ʋ ø 48 mm (1.89 in)
up to 20 m (65.62 ft)
Ʋ ø 75 mm (2.953 in)
up to 40 m (131.2 ft)
Ʋ ø 95 mm (3.74 in)
up to 50 m (164 ft)
Ʋ Parabolic antenna
up to 75 m (246.1 ft)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Installation reference conditions
Ʋ Min. distance to installations
> 200 mm (7.874 in)
Ʋ Reflector
Plane plate reflector
Ʋ False reflections
Largest false echo 20 dB smaller than the useful echo
Deviation with liquids
See following diagrams