VEGA VEGAFLEX 81 4 … 20 mA_HART two-wire Coax probe User Manual

Page 78

Advertising
background image

78

11 Supplement

VEGAFLEX 81 • 4 … 20 mA/HART two-wire

42279-EN-130612

Gas phase

Temperature

Pressure

1 bar (14.5 psig)

10 bar (145 psig)

50 bar (725 psig)

Hydrogen

20 °C/68 °F

-0.01 %

0.10 %

0.61 %

200 °C/392 °F

-0.02 %

0.05 %

0.37 %

400 °C/752 °F

-0.02 %

0.03 %

0.25 %

Steam (saturated

steam)

100 °C/212 °F

0.26 %

-

-

180 °C/356 °F

0.17 %

2.1 %

-

264 °C/507 °F

0.12 %

1.44 %

9.2 %

366 °C/691 °F

0.07 %

1.01 %

5.7 %

Characteristics and performance data
Measuring cycle time

< 500 ms

Step response time

9)

≤ 3 s

Max. filling/emptying speed

1 m/min

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +80 °C (-40 … +176 °F)

Process conditions
For the process conditions, please also note the specifications on the type label. The lowest value

always applies.
The measurement error from the process conditions is in the specified pressure and temperature

range of below 1 %.
Process pressure

Ʋ Standard version

-1 … +40 bar/-100 … +4000 kPa (-14.5 … +580 psig),

depending on the process fitting

Ʋ with borosilicate glass leadthrough

-1 … +100 bar/-100 … +10000 kPa

(-14.5 … +1450 psig), depending on the process fitting

Vessel pressure relating to the flange

nominal stage

see supplementary instructions manual "Flanges ac-

cording to DIN-EN-ASME-JIS"

Process temperature (thread or flange temperature)

Ʋ FKM (SHS FPM 70C3 GLT)

-40 … +150 °C (-40 … +302 °F)

Ʋ EPDM (A+P 75.5/KW75F)

-40 … +150 °C (-40 … +302 °F)

Ʋ FFKM (Kalrez 6375)

-20 … +150 °C (-4 … +302 °F)

Ʋ FFKM (Kalrez 6375)

-20 … +200 °C (-4 … +392 °F)

Ʋ with borosilicate glass leadthrough

-60 … +150 °C (-76 … +302 °F)

9)

Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk

solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).