9 Diagnostics and service

VEGAFLEX 81 • Foundation Fieldbus

44218-EN-130910

Measurement error during filling

Fault description

Error pattern

Cause

Rectification

3. Measured value

jumps towards 0 %

during filling

Level

time

0

– Amplitude of a multiple echo

(vessel top - product surface) is

larger than the level echo

– Check parameter "Application",

especially vessel top, type

of medium, dished end, high

dielectric constant, adapt if

necessary

– The level echo cannot be distin-

guished from the false echo at

a false echo position (jumps to

multiple echo)

– In case of interferences due to

installations in the close range:

Change polarisation direction

– Chose a more suitable installa-

tion position

– Transverse reflection from an

extraction funnel, amplitude of

the transverse reflection larger

than the level echo

– Direct sensor to the opposite

funnel wall, avoid crossing with

the filling stream

4. Measured val-

ue fluctuates around

10 … 20 %

Level

time

0

– Various echoes from an uneven

product surface, e.g. a material

cone

– Check parameter "Type of

medium" and adapt, if neces-

sary

– Optimize installation position

and sensor orientation

– Reflections from the product

surface via the vessel wall

(deflection)

– Select a more suitable installa-

tion position, optimize sensor

orientation, e.g. with a swivel-

ling holder

5. Measured value

jumps sporadically to

100 % during filling

Leve

l

time

0

– Varying condensation or con-

tamination on the antenna

– Carry out a false signal sup-

pression or increase false

signal suppression with con-

densation/contamination in the

close range by editing

– With bulk solids use radar sen-

sor with purging air connection

or flexible antenna cover

Measurement error during emptying

Fault description

Error pattern

Cause

Rectification

6. Measured value re-

mains unchanged in

the close range during

emptying

Level

time

0

– False echo larger than the level

echo

– Level echo too small

– Remove false echoes in the

close range. Check: Antenna

must protrude out of the socket

– Remove contamination on the

antenna

– In case of interferences due to

installations in the close range:

Change polarisation direction

– After removing the false ech-

oes, the false signal suppres-

sion must be deleted. Carry out

a new false signal suppression