63

11 Supplement

VEGABAR 86 • Profibus PA

45042-EN-131107

Time format

12 h/24 h

Time zone Ex factory

CET

Rate deviation max.

10.5 min/year

Measurement electronics temerature
Resolution

1 °C (1.8 °F)

Accuracy

±1 °C (1.8 °F)

Voltage supply
Operating voltage

Ʋ Non-Ex, Ex-d instrument

9 … 32 V DC

Ʋ EEx-ia instrument - Power supply

FISCO model

9 … 17.5 V DC

Ʋ EEx-ia instrument - Power supply

ENTITY model

9 … 24 V DC

Number of sensors per DP/PA segment coupler, max.

Ʋ Non-Ex

32

Ʋ Ex

10

Potential connections in the instrument
Electronics

Not non-floating

Ground terminal

Galvanically connected with the process fitting

Electrical protective measures

Housing material

Version

IP-protection class

NEMA protection

Plastic

Single chamber

IP 66/IP 67

NEMA 4X/6P

Double chamber

IP 66/IP 67

NEMA 4X

Aluminium

Single chamber

IP 66/IP 68 (0.2 bar)
IP 68 (1 bar)

NEMA 4X/6P
-

Double chamber

IP 66/IP 67
IP 66/IP 68 (0.2 bar)

NEMA 4X
NEMA 4X

Stainless steel, electro-

polished

Single chamber
Single chamber

IP 69K
IP 66/IP 68 (0.2 bar)

-
NEMA 4X/6P

Stainless steel, investment

casting

Single chamber

IP 66/IP 68 (0.2 bar)
IP 68 (1 bar)

NEMA 4X/6P
NEMA 4X

Double chamber

IP 66/IP 67
IP 66/IP 68 (0.2 bar)

NEMA 4X
NEMA 4X

Stainless steel

Transmitter for external

housing

IP 68 (25 bar)

-

Overvoltage category

III

Protection class

II

Advertising