6 Set up with the display and adjustment module

VEGAFLEX 81 • Profibus PA

44217-EN-130910

Dielectric constant - upper medium

In this menu item, you can define the type of medium (product).
Max. adjustment

In this menu item, you can enter the max. adjustment for the level.
Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.
Min. adjustment

In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

Max. adjustment - Interface

Carry out the max. adjustment for the interface.
To do this, enter the percentage value and the suitable distance value

in m for the full vessel.
Min. adjustment - Interface

Carry out the min. adjustment for the interface.
To do this, enter the percentage value and the suitable distance value

in m for the empty vessel.

Linearization

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. a horizontal cylindri-

cal or spherical tank, when the indication or output of the volume is

required. Corresponding linearization curves are preprogrammed

for these vessels. They represent the correlation between the level

percentage and vessel volume.
The linearization applies for the measured value indication and the

current output. By activating the suitable curve, the percentage vessel

volume is displayed correctly.

Interface measurement

Linearization