6 Setup

VEGATOR 111 •

46105-EN-131217

Yellow

– Relay control lamp

– The yellow relay control lamp reacts depending on the set

mode

– The relay control lamp generally indicates the activated (ener-

gized) condition of the relay

– A dark relay control lamp means that the relay is deenergised

The DIL switch block is located behind the front cover. The individual

switches are assigned as follows:

1
2

max

min

Fig. 3: DIL switch VEGATOR 111
1 Mode (min./max. adjustment)

2 Line monitoring Off/On

The requested operating mode is set with the min./max. switch (min.

detection i.e. dry run protection or max. detection i.e. overfill protec-

tion)

Dry run protection: Relay is switched off when the level falls

below the min. level (safe currentless state), relay is switched on

again when the max. level is exceeded (switch-on point > switch-

off point)

Overflow protection: Relay is switched off when the max. level is

exceeded (safe currentless state), relay is switched on again when

the level falls below the min. level (switch-on point < switch-off

point)

Note:

The mode selection on the signal conditioning instrument only func-

tions correctly if the mode switch on the sensor is set to "Max.".

When NAMUR level switches are connected, the line monitoring func-

tion can check the input continuously for line break or short-circuit. If

a mechanical switch, e.g. a float switch, is to be connected, the line

monitoring must be deactivated because only the switching condi-

tions "open" or "closed" can be delivered.

When level switches VEGASWING/VEGAVIB/VEGAWAVE in two-wire

version are connected, a function test can be carried out. The test key

is recessed behind the front plate of the signal conditioning instru-

ment. Press the test key for at least one second with a suitable object

(screwdriver, pen, etc.).
Pushing the test key interrupts the circuit to the sensor and triggers a

restart of the sensor. The statuses fault signal, full signal (1.2 mA) and

empty signal (2.1 mA) are thus simulated. Check if a fault signal (red

signal lamp) is triggered when the test key is pressed and then a full

signal and subsequent empty signal (yellow signal lamp) after the key

DIL switch block

Mode (min./max. adjust-

ment)

Line monitoring

Test key