11 Supplement

VEGAFLEX 81 • Modbus and Levelmaster protocol

42283-EN-130314

Ʋ Vessel

metallic, ø 1 m (3.281 ft), centric installation, process

fitting flush with the vessel ceiling

Ʋ Medium

Water/Oil (dielectric constant ~2.0)

2)

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

Gating out of false signals carried out

Typical deviation - Interface measure-

ment

± 5 mm (0.197 in)

Typical deviation - Total level interface

measurement

± 5 mm (0.197 in)

Typical deviation - Level measurement

3)4)

See following diagrams

Max. deviation - Version with reference

distance

± 10 mm (0.39 in)

Deviating upper dead band - Version with

reference distance

450 mm (17.7 in)

L

0

-2 mm (-0.079")

2 mm (0.079")

-10 mm (0.394")

5 mm (0.197")

0,15 m (5.906")

0,03 m (1.181")

0,05 m

(1.969")

1

Fig. 32: Deviation VEGAFLEX 81 in coax version in water
1 Dead band - no measurement possible in this area

L Probe length

2)

with interface measurement = 2.0

3)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode

4)

The dead bands can be optimizes by a false signal suppression.