6 Set up with the display and adjustment module
VEGAFLEX 82 • 4 … 20 mA/HART two-wire
41829-EN-130612
Since scaling is very extensive, scaling of the level value was divided
into two menu items.
In menu item "Level 2" you define the scaling format on the display
and the scaling of the measured level value for 0 % and 100 %.
In menu item"Current output, size" you determine which measured
value the current output refers to.
In menu item "Current output, adjustment" you can assign a respec-
tive measured value to the current output.
In the menu item "Current output mode" you determine the output
characteristics and reaction of the current output in case of failure.
The default setting is output characteristics 4 … 20 mA, failure mode
< 3.6 mA.
In the menu item "Current output Min./Max.", you determine the reac-
tion of the current output during operation.
Setup - Scaling Level 2
Setup - Current output
Size
Setup - Current output,
adjustment
Setup/Current output
mode
Setup - Current output
Min./Max.