6 Set up with the display and adjustment module

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

41829-EN-130612

Since scaling is very extensive, scaling of the level value was divided

into two menu items.

In menu item "Level 2" you define the scaling format on the display

and the scaling of the measured level value for 0 % and 100 %.

In menu item"Current output, size" you determine which measured

value the current output refers to.

In menu item "Current output, adjustment" you can assign a respec-

tive measured value to the current output.

In the menu item "Current output mode" you determine the output

characteristics and reaction of the current output in case of failure.

The default setting is output characteristics 4 … 20 mA, failure mode

< 3.6 mA.

In the menu item "Current output Min./Max.", you determine the reac-

tion of the current output during operation.

Setup - Scaling Level 2

Setup - Current output

Size

Setup - Current output,

adjustment

Setup/Current output

mode

Setup - Current output

Min./Max.