9 Diagnosis, Asset Management and service

VEGAPULS SR 68 • HART and accumulator pack

40934-EN-130624

Constant level

Filling

Emptying

The images in column "Error pattern" show the real level with a bro-

ken line and the level displayed by the sensor as a continuous line.

1
2

Level

time

0

1 Real level

2 Level displayed by the sensor

Notes:

Wherever the sensor displays a constant value, the reason could

also be the fault setting of the current output to "Hold value"

In case of a too low level indication, the reason could be a line

resistance that is too high

Measurement error with constant level

Fault description

Error pattern

Cause

Rectification

1. Measured value

shows a too low or too

high level

Level

time

0

– Min./max. adjustment not

correct

– Adapt min./max. adjustment

– Wrong linearization curve

– Adapt linearization curve

2. Measured value

jumps towards 100 %

Level

time

0

– Due to the process, the ampli-

tude of the product echo sinks

– A false signal suppression was

not carried out

– Carry out a false signal sup-

pression

– Amplitude or position of a

false echo has changed (e.g.

condensation, buildup); false

signal suppression no longer

matches

– Determine the reason for the

changed false echoes, carry

out false signal suppression,

e.g. with condensation