4 level measurement – VEGA VEGABAR 81 4 … 20 mA - Operating Instructions User Manual

Page 17

Advertising
background image

17

4 Mounting

VEGABAR 81 • 4 … 20 mA

45025-EN-131010

A protective accumulation of water is formed through condensation

in the pipe bends. Even in applications with hot steam, a medium

temperature < 100 °C on the transmitter is ensured.

Keep the following in mind when setting up the measuring system:

Mount the instrument below the measuring point

The effective pressure line is always filled with liquid and gas bubbles

can bubble up to the process line.

3

1

2

Fig. 11: Measurement setup for process pressure measurement of liquids in

pipelines
1 VEGABAR 81

2 Blocking valve

3 Pipeline

4.4 Level measurement

Keep the following in mind when setting up the measuring system:

Mount the instrument below the min. level

Do not mount the instrument close to the filling stream or emptying

area

Mount the instrument so that it is protected against pressure

shocks from the stirrer

Fig. 12: Measurement setup for level measurement

Measurement setup in

liquids

Measurement setup